phone: 704.821.6651
fax: 704.821.7999


Changing Image
: Yaskawa >>    GA500 HOME SEARCH CONTACTS SITE MAP
Thursday, October 10, 2024

SpecificationsDocumentation






The GA500 Industrial AC Microdrive is engineered to help you easily handle nearly any application. Sustainability, flexibility, and ease of use are all designed into the drive, helping you make complicated tasks simple. Offering intuitive interaction and world-class quality, the GA500 is the drive you can count on for constant, high quality performance.


Specifications
  • Ratings:1/6 to 5 HP at 240 VAC 1-ph
    1/6 to 30 HP (ND) at 240 VAC
    1/2 to 40 HP (ND) at 480 VAC
  • Overload Capacity:
    150% for 60 sec. (HD)
    110% for 60 Sec. (ND)
  • Output frequency: 0 ~ 590 Hz
  • Control Methods:
    Open Loop V/f
    Open loop Current Vector
  • Motor Types:
    Induction
    Surface Permanent Magnet
    Interior Permanent Magnet
    Synchronous Reluctance
  • Protective Design:
    IP20/Protected Chassis
    IP20/UL Type 1 kit available
  • Ambient Operating Temperature:
    -10 to +50°C (IP20/Protected Chassis)
    -10 to +40°C (with UL Type 1 kit)
    up to +60°C with derate
  • Global Certification: UL, CE, RCM, RoHS
  • Functional Safety: Safe Torque Off, SIL3 according to IEC 62061, PLe according to ISO 13849-1
  • Standard I/O:
    (7) multi-function digital inputs (24 VDC)
    (2) multi-function analog inputs (0 +/- 10 VDC, 4-20 mA)
    (1) multi-function pulse inputs
    (2) Safe Torque Off inputs
    (1) fault relay output (form C)
    (2) multi-function outputs (photocoupler)
    (1) multi-function analog output (0 to 10 VDC / 4 to 20 mA)
    (1) multi-function pulse output
  • Network Communication
    Embedded: Modbus RTU, RS-485, 115 kbps
    Optional: EtherNet/IP, DeviceNet, Modbus TCP/IP, PROFINET, PROFIBUS-DP, EtherCAT, MECHATROLINK-II, MECHATROLINK-III
  • Speed Control Range:
    200:1 Open Loop Vector (IM Motors)
    100:1 Open Loop Vector (PM Motors)
  • Speed Control Accuracy: ≤ 0.2%; Open Loop Vector
  • Speed Response:
    ≥ 20 Hz: Open Loop Vector (Induction Motors)
    ≥ 40 Hz: Open Loop Vector (PM Motors)
  • Function Block Diagrams: Up to 100 connections, 1ms program scan time


  • Features
    • No power programming
    • Intuitive keypad
    • Conformal coated (IEC 60721-3-3: 3C2, 3S2)
    • Up to 30% smaller than the competition
    • Current vector control, open loop
    • Induction motor (IM), permanent magnet motor (PM), or synchronous reluctance motor operation
    • SIL3 (IEC 62061), PLe (ISO 13849-1) safety ratings
    • Embedded Modbus communication
    • Wide variety of communication options
    • Variety of mounting methods (standard, IP20/UL Type 1, side-by-side, external heatsink, DIN rail)
    • Embedded 24 Vdc power supply
    • Maintenance monitors
    • Cooling fan replacement without tools
    • Optional LCD or Bluetooth keypad
    • Global certifications (CE, UL, cUL, TUV, RCM)
    • MTBF: 28 years
    • Short Circuit Current Rating (SCCR): 31 kA rms symmetrical
    • Common programming with all other Yaskawa drives
    • DriveWizard Industrial software for parameter management and start-up
    • DriveWizard Mobile application for smartphones and tablets
    • Function Block Diagram (FBD) programming via DriveWorksEZ™



REV DATE: 05/27/2021


©2024 SCR Controls, Inc.
3479 Gribble Rd., Matthews, NC 28104
PO Box 2368, Indian Trail, NC 28079
email: info@scrcontrols.com

By viewing this site you agree with Terms of Use.

This sight is viewed best viewed with the latest versions of Edge and Chrome.


A. Manufactured items:
MELLTRUM (SPECTRUM REPLACEMENT) ES100A ES125A ES150A ES150ARG ES200A ES200ARG ES222 ES2300RG ES2600RG ES2700 2400-8000 2400-8001W 2450-8000W 2450-8001W 2450-8010W 2450-8015W EDDY CURRENT CLUTCH 1235 367 FOCUS 2 FOCUS1 FOCUS 1 REPLACEMENT BOULIGNY MARK ANDY SECO BALDWIN ENKEL CUSTOM AUTOMATION SYSTEMS MULTI DRIVE SYSTEMS ERC REPLACEMENT.